Study on the Spatial and Temporal Evolution of Hydrogen-Blended Natural Gas Leakage and Flare-Up in the Typical Semi-Open Space
Abstract
Numerical simulations reveal the combustion dynamics of hydrogen-blended natural gas (H-BNG) in semi-open spaces. In the typical semi-open space scenario, increasing the hydrogen blending ratio from 0% to 60% elevates peak internal pressure by 107% (259.3 kPa → 526.0 kPa) while reducing pressure rise time by 56.5% (95.8 ms → 41.7 ms). A vent size paradox emerges: 0.5 m openings generate 574.6 kPa internal overpressure, whereas 2 m openings produce 36.7 kPa external overpressure. Flame propagation exhibits stabilized velocity decay (836 m/s → 154 m/s, 81.6% reduction) at hydrogen concentrations ≥30% within 2–8 m distances. In street-front restaurant scenarios, 80% H-BNG leaks reach alarm concentration (0.8 m height) within 120 s, with sensor response times ranging from 21.6 s (proximal) to 40.2 s (distal). Forced ventilation reduces hazard duration by 8.6% (151 s → 138 s), while door status shows negligible impact on deflagration consequences (412 kPa closed vs. 409 kPa open), maintaining consistent 20.5 m hazard radius at 20 kPa overpressure threshold. These findings provide crucial theoretical insights and practical guidance for the prevention and management of H-BNG leakage and explosion incidents.