Safety
Experimental Study on the Operation of Pressure Safety Valve in the Liquid Hydrogen Environment
Sep 2025
Publication
In this study a liquid hydrogen (LH2) safety valve evaluation device was developed to enable safe and stable performance testing of pressure safety valves (PSVs) under realistic cryogenic and high-pressure conditions. The device was designed for flexible use by mounting all components on a mobile frame equipped with wheels and the pressurization rate inside the vessel was controlled through a boil-off gas (BOG) generator. Two experiments were conducted to investigate the effect of LH2 production rate on PSV operation. When the production of LH2 increased by about 2.4 times the number of PSV operations rose from 15 to 20 and the operating pressure range shifted slightly upward from 10.68~12.53 bar to 10.68~13.2 bar while remaining within the instrument’s error margin. These results indicate that repeated valve cycling and increased hydrogen production contribute to gradual changes in PSV operating characteristics. Additionally the minimum temperature experienced by the PSV decreased with repeated operations reaching approximately 77.9 K. The developed evaluation system provides an effective platform for analyzing PSV performance under realistic LH2 production and storage conditions.
IEA TCP Task 43 - Recommendations for Safety Distances Methodology for Alkaline and PEM Electrolyzers
Sep 2025
Publication
Elena Vyazmina,
Richard Chang,
Benjamin Truchot,
Katrina M. Groth,
Samantha E. Wismer,
Sebastien Quesnel,
David Torrado,
Nicholas Hart,
Thomas Jordan,
Karen Ramsey-Idem,
Deborah Houssin-Agbomson,
Simon Jallais,
Christophe Bernard,
Lucie Bouchet,
Ricardo Ariel Perez,
Lee Phillips,
Marcus Runefors,
Jerome Hocquet and
Andrei V. Tchouvelev
Currently local regulations governing hydrogen installations vary by geographical region and by country leading to discrepancies in safety and separation distance requirements for similar hydrogen systems. This work carried out in the frame of IEA TCP H2 Task 43 (IEA TCP H2 2022) aims to provide an overview of various methodologies and recommendations established for risk management and consequence assessment in the event of accidental scenarios. It focuses on a case study involving industrial electrolyzers utilizing alkaline and PEM technologies. The research incorporates lessons learned from past incidents offers recommendations for mitigation measures reviews existing methodologies and highlights areas of divergence. Additionally it proposes strategies for harmonization. The study also emphasizes the most significant scenarios and the corresponding leakage sizes
Safety Analysis of Hydrogen-Powered Train in Different Application Scenarios: A Review
Mar 2025
Publication
Currently there are many gaps in the research on the safety of hydrogen-powered trains and the hazardous points vary across different scenarios. It is necessary to conduct safety analysis for various scenarios in order to develop effective accident response strategies. Considering the implementation of hydrogen power in the rail transport sector this paper reviews the development status of hydrogen-powered trains and the hydrogen leak hazard chain. Based on the literature and industry data a thorough analysis is conducted on the challenges faced by hydrogen-powered trains in the scenario of electrified railways tunnels train stations hydrogen refueling stations and garages. Existing railway facilities are not ready to deal with accidental hydrogen leakage and the promotion of hydrogen-powered trains needs to be cautious.
Evaluation of Passenger Train Safety in the Event of a Liquid Hydrogen Release from a Freight Train in a Tunnel Along an Italian High-Speed/High-Capacity Rail Line
Oct 2025
Publication
The global shift towards cleaner energy sources is driving the adoption of hydrogen as an environmentally friendly alternative to fossil fuels. Among the forms currently available Liquid Hydrogen (LH2) offers high energy density and efficient storage making it suitable for large-scale transport by rail. However the flammability of hydrogen poses serious safety concerns especially when transported through confined spaces such as railway tunnels. In case of an accidental LH2 release from a freight train the rapid accumulation and potential ignition of hydrogen could cause catastrophic consequences especially if freight and passenger trains are present simultaneously in the same tunnel tube. In this study a three-dimensional computational fluid dynamics model was developed to simulate the dispersion and explosion of LH2 following an accidental leak from a freight train’s cryo-container in a single-tube double-track railway tunnel when a passenger train queues behind it on the same track. The overpressure results were analyzed using probit functions to estimate the fatality probabilities for the passenger train’s occupants. The analysis suggests that a significant number of fatalities could be expected among the passengers. However shorter users’ evacuation times from the passenger train’s wagons and/or longer distances between the two types of trains might reduce the number of potential fatalities. The findings by providing additional insight into the risks associated with LH2 transport in railway tunnels indicate the need for risk mitigation measures and/or traffic management strategies.
Numerical Investigation of Hydrogen Leakage Quantification and Dispersion Characteristics in Buried Pipelines
Sep 2025
Publication
As a clean energy carrier hydrogen is essential for global low-carbon energy transitions due to its unique combination of safe transport properties and energy density. This investigation employs computational fluid dynamics (ANSYS Fluent) to systematically characterize hydrogen dispersion through soil media from buried pipelines. The research reveals three fundamental insights: First leakage orifices smaller than 2 mm demonstrate restricted hydrogen migration regardless of directional orientation. Second dispersion patterns remain stable under both low-pressure conditions (below 1 MPa) and minimal thermal gradients with pipeline temperature variations limited to 63 K and soil fluctuations under 40 K. Third dispersion intensity increases proportionally with higher leakage pressures (exceeding 1 MPa) greater soil porosity and larger particle sizes while inversely correlating with burial depth. The study develops a predictive model through Sequential Quadratic Programming (SQP) optimization demonstrating exceptional accuracy (mean absolute error below 10%) for modeling continuous hydrogen flow through moderateporosity soils under medium-to-high pressure conditions with weak inertial effects. These findings provide critical scientific foundations for designing safer hydrogen transmission infrastructure establishing robust risk quantification frameworks and developing effective early-warning systems thereby facilitating the practical implementation of hydrogen energy systems.
Technoeconomic analysis of Hydrogen Versus Natural Gas Considering Safety Hazards and Energy Efficiency Indicators
Aug 2025
Publication
Hydrogen (H2) is emerging as a key alternative to fossil fuels in the global energy transition. This study presents a comparative techno-economic analysis of H2 and natural gas (NG) focusing on safety hazards energy output CO2 emissions and cost-effectiveness aspects. Our analysis showed that compared to NG and other highly flammable gases like acetylene (C2 H2) and propane (C3 H8) H2 has a higher hazard potential due to factors such as its wide flammability range low ignition energy and high flame speed. In terms of energy output 1 kg of NG produces 48.60 MJ while conversion to liquefied natural gas (LNG) grey H2 and blue H2 reduces energy output to 45.96 MJ 35.45 MJ and 31.21 MJ respectively. Similarly while unconverted NG emits 2.72 kg of CO2 per kg emissions increase to 3.12 kg for LNG and 3.32 kg for grey H2. However blue H2 significantly reduces CO2 emissions to 1.05 kg per kg due to carbon capture and storage. From an economic perspective producing 1 kg of NG yields a profit of $0.011. Converting NG to grey H2 is most profitable yielding a net profit of $0.609 per kg of NG while blue H2 despite higher production costs remains viable with a profit of $0.390 per kg of NG. LNG conversion also shows profitability with $0.061 per kg of NG. This analysis highlights the trade-offs between energy efficiency environmental impact and economic viability providing valuable insights for stakeholders formulating hydrogen and LNG implementation strategies.
Research on Hydrogen Leakage Risk Control Methods in Deck Compartments of Hydrogen Fuel Cell-Powered Ships Based on CFD Simulation and Ventilation Optimization
Oct 2025
Publication
Hydrogen fuel cell vessels represent a vital direction for green shipping but the risk of large-scale hydrogen leakage and diffusion in their enclosed compartments is particularly prominent. To enhance safety a simplified three-dimensional model of the deck-level cabins of the “Water-Go-Round” passenger ship was established using SolidWorks (2023) software. Based on a hydrogen leakage and diffusion model the effects of leakage location leakage aperture and initial ambient temperature on the diffusion patterns and distribution of hydrogen within the cabins were investigated using FLUENT software. The results show that leak location significantly affects diffusion direction with hydrogen leaking from the compartment ceiling diffusing horizontally much faster than from the floor. When leakage occurs at the compartment ceiling hydrogen can reach a maximum horizontal diffusion distance of up to 5.04 m within 540 s; the larger the leak aperture the faster the diffusion with a 10 mm aperture exhibiting a 40% larger diffusion range than a 6 mm aperture at 720 s. The study provides a theoretical basis for the safety design and risk prevention of hydrogen fuel cell vessels.
A Proposal of Hydrogen Safety Technology for Decommissioning of the Fukushima Daiichi Nuclear Power Station
Mar 2025
Publication
The safe removal transportation and long-term storage of fuel debris in the decommissioning of Fukushima Daiichi is the biggest challenge facing Japan. In the nuclear power field passive autocatalytic recombiners (PARs) have become established as a technology to prevent hydrogen explosions inside the containment vessel. To utilize PAR as a measure to reduce the concentration of hydrogen generated in the fuel debris storage canister which is currently an issue it is required to perform in a sealed environment with high doses of radiation low temperature and high humidity and there are many challenges different from conventional PAR. A honeycombshaped catalyst based on automotive catalyst technology has been newly designed as a PAR and research has been conducted to solve unique problems such as high dose radiation low temperature high humidity coexistence of hydrogen and low oxygen and catalyst poisons. This paper summarizes the challenges of hydrogen generation in a sealed container the results of research and a guide to how to use the PAR for fuel debris storage canisters.
Interfacial Damage Evolution in Hygrothermally Aged CF/PPA Composites used in Type V Hydrogen Tanks: A Multi-scale Approach
Nov 2025
Publication
This paper presents a multi-scale experimental investigation into the damage mechanisms in carbon fiberreinforced polyphthalamide (CF/PPA) composites subjected to hygrothermal aging. The study specifically targets their suitability for structural components in advanced hydrogen storage systems such as Type V pressure vessels. Polyphthalamides (PPAs) as semi-aromatic polyamides offer superior thermal stability chemical resistance and mechanical performance compared to conventional aliphatic polyamides making them promising candidates for structural components exposed to harsh environments. In order to simulate more severe environmental exposure accelerated hygrothermal aging tests were conducted at 50 ◦C in immersion. A range of microscopic to macroscopic characterization techniques were used to assess changes in mechanical performance and microstructural integrity. The analysis revealed that the CF/PPA composites retained good matrix ductility even after aging indicating the resilience of the semi-aromatic polyamide matrix under hygrothermal stress. Multi-scale damage analysis has been performed on both unaged and aged samples at 50 ◦C for various aging times. The dominant damage mechanism identified was decohesion at the fiber/matrix interface rather than bulk matrix degradation. This interfacial debonding has a significant impact on mechanical performance and is attributed to moisture-induced weakening of interfacial interactions. These findings emphasize the potential of CF/PPA composites for use in high-performance hydrogen storage applications while highlighting the critical need for interface-tailored designs to enhance environmental durability.
A Review on Combustion Instability of Hydrogen-Enriched Marine Gas Turbines
Nov 2025
Publication
Hydrogen is widely regarded as a promising carbon-free alternative fuel. However the development of low-emission marine gas turbine combustion systems has been hindered by the associated risks of combustion instability also termed as thermoacoustic oscillations. Although there is sufficient literature on hydrogen fuel and combustion instability systematic reviews addressing the manifestations and mechanisms of these instabilities remain limited. The present study aims to provide a comprehensive review of combustion instabilities in hydrogen-enriched marine gas turbines with a particular focus on elucidating the characteristics and underlying mechanisms. The review begins with a concise overview of recent progress in understanding the fundamental combustion properties of hydrogen and then details various instability phenomena in hydrogen-enriched methane flames. The mechanisms by which hydrogen enrichment affects combustion instabilities are extensively discussed particularly in relation to the feedback loop in thermoacoustic combustion systems. The paper concludes with a summary of the key combustion instability challenges associated with hydrogen addition to methane flames and offers prospects for future research. In summary the review highlights the interaction between hydrogenenriched methane flames and thermoacoustic phenomena providing a foundation for the development of stable low-emission combustion systems in industrial marine applications incorporating hydrogen enrichment.
Dispersion of High-Pressure Hydrogen Jets in Open-Top and Indoor Environments: Effects of Leak Geometry and Pressure
Nov 2025
Publication
Yang Li,
Shourui Zhang,
Meng Yu,
Yang Wu,
Jiake Wu and
Long Jiang
Hydrogen leakage is a critical safety concern for high-pressure storage systems where orifice geometry significantly influences dispersion and risk. Previous studies on leakage and diffusion have mostly focused on closed or semi-closed environments while thorough exploration has been conducted on open and unshielded environments. This work compares three typical orifice types—circular slit and Y-type—through controlled experiments. Results show that circular orifices generate directional jets with steep gradients but relatively low concentrations with a 1 mm case reaching only 0.725% at the jet core. Slit orifices exhibit more uniform diffusion; at 1 mm concentrations ranged from 2.125% to 2.625%. Y-type orifices presented the highest hazard with 0.5 mm leaks producing 2.9% and 1 mm cases approaching the 4% lower flammability limit within 375 s. Equilibrium times increased with orifice size from 400–800 s for circular and slit leaks to up to 900 s for Y-type leaks some of which failed to stabilize. Response behavior also varied: Y-type leaks achieved rapid multi-point responses (as short as 10 s) while circular and slit leaks responded more slowly away from the jet core. Overall risk ranking was circular < slit < Y-type underscoring the urgent need for geometry-specific monitoring strategies sensor layouts and emergency thresholds to ensure safe hydrogen storage.
351 Hazardous Area Impact Mitigation Phase 1
Mar 2026
Publication
Steer Energy and
SGN
This programme of work aims to generate empirical evidence of gas concentration with respect to distance from the vent tip for a range of hydrogen releases. The measured data is to be compared to the Zone 2 exclusion distances specified by the IGEM/SR/25 hydrogen supplement.
Test cases have been shared with Steer Energy that calculate the new hazardous areas as per the hydrogen supplement for common infrastructure such as pressure regulating installations/stations. The result of these test cases was a significant increase in the calculated hazardous zone distances for hydrogen compared to those for Natural Gas. The overall programme aims are to measure gas releases replicating these test cases and to compare the measured hazardous zones to the calculated hazardous zones. This report covers Stage 1 of the programme of work which comprised an initial examination using small releases as a fast and economical method to assess the likelihood of differences between measured and calculated zones.
Experimental equipment was setup to release gas at controlled flow rates to match those of the IGEM/SR/25 hydrogen supplement tables. A moveable array of gas detectors was positioned above the vent tip to measure the shape and magnitude of the resulting gas plume from the release.
In all 22 tests were conducted with gas released from two different vent diameters 13 mm and 48 mm. Two gas types hydrogen and methane were used. Ideal and non-ideal vents were tested across a limited range of flows. The measured data enabled colourmaps of the vents to be created showing the shape and magnitude of the resulting gas plumes.
The results of the study have shown that in all cases the shape of the plumes from the measured vents are significantly different to the dispersion distances specified in the relevant tables of IGEM/SR/25. In most cases no gas was detected throughout the majority of the specified hazardous area instead a thin vertical cylindrical plume of gas was measured often extending above the specified dispersion zones. This was seen in both hydrogen and methane tests.
The test results from this initial phase of the project cast some doubt on the findings from the previous NIA project ATEX Equipment & SR/25 Modification Assessment that used the SR/25 calculator developed from the hydrogen supplement tables. In some instances the horizontal dispersion distance for hydrogen was calculated to be over 6 times the value for Natural Gas (see Figure 2) with its resulting hazardous area exclusion zone having potentially serious consequences on the viability of the corresponding AGIs without mitigations. However results from the initial tests undertaken during this phase of work demonstrate significant inconsistencies between the calculated results and empirical tests. This should be further investigated in phase 2 as initial conclusions show that the larger hazardous zones mentioned above are seemingly overstating the risk. The previous work also modelled the hazardous areas using full bore releases whereas relief valves on the network tend to incorporate flow limiting orifices therefore further exacerbating the perceived increased risk.
This report was submitted to HSE for their assessment of the safety evidence for 100% hydrogen heating which can be found at Hydrogen heating: HSE assessment of the safety evidence - GOV.UK.
Queries should be directed to DESNZ: https://www.gov.uk/guidance/contact-desnz.
Test cases have been shared with Steer Energy that calculate the new hazardous areas as per the hydrogen supplement for common infrastructure such as pressure regulating installations/stations. The result of these test cases was a significant increase in the calculated hazardous zone distances for hydrogen compared to those for Natural Gas. The overall programme aims are to measure gas releases replicating these test cases and to compare the measured hazardous zones to the calculated hazardous zones. This report covers Stage 1 of the programme of work which comprised an initial examination using small releases as a fast and economical method to assess the likelihood of differences between measured and calculated zones.
Experimental equipment was setup to release gas at controlled flow rates to match those of the IGEM/SR/25 hydrogen supplement tables. A moveable array of gas detectors was positioned above the vent tip to measure the shape and magnitude of the resulting gas plume from the release.
In all 22 tests were conducted with gas released from two different vent diameters 13 mm and 48 mm. Two gas types hydrogen and methane were used. Ideal and non-ideal vents were tested across a limited range of flows. The measured data enabled colourmaps of the vents to be created showing the shape and magnitude of the resulting gas plumes.
The results of the study have shown that in all cases the shape of the plumes from the measured vents are significantly different to the dispersion distances specified in the relevant tables of IGEM/SR/25. In most cases no gas was detected throughout the majority of the specified hazardous area instead a thin vertical cylindrical plume of gas was measured often extending above the specified dispersion zones. This was seen in both hydrogen and methane tests.
The test results from this initial phase of the project cast some doubt on the findings from the previous NIA project ATEX Equipment & SR/25 Modification Assessment that used the SR/25 calculator developed from the hydrogen supplement tables. In some instances the horizontal dispersion distance for hydrogen was calculated to be over 6 times the value for Natural Gas (see Figure 2) with its resulting hazardous area exclusion zone having potentially serious consequences on the viability of the corresponding AGIs without mitigations. However results from the initial tests undertaken during this phase of work demonstrate significant inconsistencies between the calculated results and empirical tests. This should be further investigated in phase 2 as initial conclusions show that the larger hazardous zones mentioned above are seemingly overstating the risk. The previous work also modelled the hazardous areas using full bore releases whereas relief valves on the network tend to incorporate flow limiting orifices therefore further exacerbating the perceived increased risk.
This report was submitted to HSE for their assessment of the safety evidence for 100% hydrogen heating which can be found at Hydrogen heating: HSE assessment of the safety evidence - GOV.UK.
Queries should be directed to DESNZ: https://www.gov.uk/guidance/contact-desnz.
MOBs Phase 3: Task 4 - Ventilation Report
Mar 2026
Publication
There is a requirement for gas distribution network (GDN) operators to understand the cost safety and practicality of converting network pipelines from Natural Gas to Hydrogen in multi-occupancy buildings (MOBs). Previous work undertaken during project ‘MOBs Work Pack 2 Asset Information Review’ [1] considered the requirements for pressure testing commissioning and decommissioning of MOBs following a conversion to Hydrogen and identified the following gaps in technical evidence.
“How does Hydrogen affect the requirements for ventilation and explosion relief?”
“Work is required to understand the ventilation requirements of meters installed inside dwellings whether existing ventilation in MOBs is adequate and the practicalities of increasing the ventilation should it be required. Work has already been undertaken under the NIA project ‘NIA_WWU_2_12 – Ventilation Within Buildings’[2]. It was proposed that ROSEN review the NIA_WWU_2_12 work and confirm its applicability to MOBs”.
"Further work is required including a study consisting of a review of relevant British Standards (BS 8313 [77] BS 6891 [75] and BS 5925 [78]) and validation through case studies to determine how duct dimensions and ventilation requirements are affected by Hydrogen. This work would also need to determine whether the size and positioning of existing vents are adequate with Hydrogen.
“Further work is required to determine whether the ventilation in dwellings is adequate for risers and laterals located within and passing through dwellings.”
SGN is leading a feasibility project with some applied testing to understand the steps needed to convert MOBs to Hydrogen including any testing required to address any evidence gaps. This report focuses on the ventilation requirements associated with the conversion of MOBs from Natural Gas to Hydrogen. The objectives of this task are to:
• Determine ventilation requirements for meters risers and laterals inside buildings.
• Determine ventilation requirements for typical meter banks and energy centres with Hydrogen and how they compare with ventilation requirements for Natural Gas and update Table 6 of IGEM/G/5 Edition 3 [2]
• Determine ventilation requirements for typical ducts with Hydrogen and how they compare with ventilation requirements for Natural Gas and update Table 8 of IGEM/G/5 Edition 3.
• Investigate the feasibility of adding ventilation to MOBs which will need to be positioned so as not to compromise fire safety if located in a fire compartment.
This report was submitted to HSE for their assessment of the safety evidence for 100% hydrogen heating which can be found at Hydrogen heating: HSE assessment of the safety evidence - GOV.UK.
Queries should be directed to DESNZ: https://www.gov.uk/guidance/contact-desnz.
“How does Hydrogen affect the requirements for ventilation and explosion relief?”
“Work is required to understand the ventilation requirements of meters installed inside dwellings whether existing ventilation in MOBs is adequate and the practicalities of increasing the ventilation should it be required. Work has already been undertaken under the NIA project ‘NIA_WWU_2_12 – Ventilation Within Buildings’[2]. It was proposed that ROSEN review the NIA_WWU_2_12 work and confirm its applicability to MOBs”.
"Further work is required including a study consisting of a review of relevant British Standards (BS 8313 [77] BS 6891 [75] and BS 5925 [78]) and validation through case studies to determine how duct dimensions and ventilation requirements are affected by Hydrogen. This work would also need to determine whether the size and positioning of existing vents are adequate with Hydrogen.
“Further work is required to determine whether the ventilation in dwellings is adequate for risers and laterals located within and passing through dwellings.”
SGN is leading a feasibility project with some applied testing to understand the steps needed to convert MOBs to Hydrogen including any testing required to address any evidence gaps. This report focuses on the ventilation requirements associated with the conversion of MOBs from Natural Gas to Hydrogen. The objectives of this task are to:
• Determine ventilation requirements for meters risers and laterals inside buildings.
• Determine ventilation requirements for typical meter banks and energy centres with Hydrogen and how they compare with ventilation requirements for Natural Gas and update Table 6 of IGEM/G/5 Edition 3 [2]
• Determine ventilation requirements for typical ducts with Hydrogen and how they compare with ventilation requirements for Natural Gas and update Table 8 of IGEM/G/5 Edition 3.
• Investigate the feasibility of adding ventilation to MOBs which will need to be positioned so as not to compromise fire safety if located in a fire compartment.
This report was submitted to HSE for their assessment of the safety evidence for 100% hydrogen heating which can be found at Hydrogen heating: HSE assessment of the safety evidence - GOV.UK.
Queries should be directed to DESNZ: https://www.gov.uk/guidance/contact-desnz.
Hazardous Area Impact Mitigations (HAIM) Phase 2a: Full Scale Testing, Interim Report
Mar 2026
Publication
This project has built on the Hazardous Area Impact Mitigation (HAIM) Phase 1 project (NIA2_SGN0041) results that identified a disparity between hazardous zones measured during initial testing and those specified in the IGEM/SR/25 Hydrogen supplement. The aim of the HAIM Phase 2 project is to scale up the measurements to confirm the behaviour of larger vents equivalent to the test cases presented in the ATEX Equipment & IGEM/SR/25 Modification Assessment (NGNG_NIA_346) project.
The formation of a technical review group has informed the project team of the parameters and some of the assumptions used for the modelling leading to the development of the SR/25 Hydrogen Supplement. The difference between the modelled and measured data seen in the HAIM Phase 1 project has been attributed to the modelled data being carried out under a minimum of 0.5 m/s cross winds. Completely still conditions are not expected to occur hence this 0.5 m/s minimum. The result of this wind on the model leads to a significant reduction of the height of the resulting plume and a corresponding increase in the radial displacement of the plume from the vent tip. This has shifted the focus of this project towards examining wind influenced vents.
Two sets of experiments are provided in this interim report: measurements of plumes from wind influenced vents and plumes from fixtures and fitting leaks. The report also includes early results from plume ignition studies which have shown that ignition is not instantaneous for high velocity plumes.
The wind influenced plume tests have measured 0.0005 kg/s hydrogen releases from 50 mm and 15 mm vent pipes. The largest hazardous zone for these releases stipulated in IGEM/SR/25 hydrogen supplement is Xr = 2.5 m and Xh = 1.5 m so these were used as the extent of measurement. With no wind the plume rises vertically from the vent tip with no radial deflection. Measured concentration peaks have exceeded the lower flammable limit (LFL) at the 1.5 m measurement height. The influence of wind radially displaces the plume the higher the wind the larger the displacement. Concentration peaks are reduced but a wind of 0.5 m/s still permitted levels above the 4 % LFL value. Wind levels of 1.0 m/s displaced the plume to the end of the 2.5 m measurement array. Wind levels of 1.5 m/s broke up the plumes potentially driving pockets of gas beyond the 2.5 m measurement array.
Partial ignition of both vent types was possible at 1.5 m above the vent tip but complete sustained ignition was only possible when closer than 1 m to the vent tip.
Plumes from higher pressure (above 0.1 barg) fixture and fitting leaks have shown a good correlation between the shapes of modelled and measured vents. Except for the lowest pressure leaks which are momentum-dominated jets the resulting plumes are long and thin unaffected by buoyancy. The concentration decay in measured plumes is observed to be faster with distance compared to modelled values. Typically the measured distance to reach 2 % volume from the leak position is about half of the specified zone distances.
Limited ignition tests have been conducted but ignition from a 2 barg adverse downward pointing leak was challenging beyond 30 cm from the leak. The hydrogen jet also repeatably extinguished the methane flame used as pilot light during tests.
The next steps for the project are to carry out more measurements and to scale up the magnitude of the gas releases. This will provide more evidence supporting specified magnitudes of hazardous zones. In addition it is proposed that mitigation measures are explored that could reduce the specified hazardous zones for given vents. This could include design guidelines for hydrogen vents.
Further ignition tests will also be conducted to assess required conditions such as flow direction and gas concentration required to achieve both partial and stable ignition of hydrogen vents.
This report was submitted to HSE for their assessment of the safety evidence for 100% hydrogen heating which can be found at Hydrogen heating: HSE assessment of the safety evidence - GOV.UK.
Queries should be directed to DESNZ: https://www.gov.uk/guidance/contact-desnz.
The formation of a technical review group has informed the project team of the parameters and some of the assumptions used for the modelling leading to the development of the SR/25 Hydrogen Supplement. The difference between the modelled and measured data seen in the HAIM Phase 1 project has been attributed to the modelled data being carried out under a minimum of 0.5 m/s cross winds. Completely still conditions are not expected to occur hence this 0.5 m/s minimum. The result of this wind on the model leads to a significant reduction of the height of the resulting plume and a corresponding increase in the radial displacement of the plume from the vent tip. This has shifted the focus of this project towards examining wind influenced vents.
Two sets of experiments are provided in this interim report: measurements of plumes from wind influenced vents and plumes from fixtures and fitting leaks. The report also includes early results from plume ignition studies which have shown that ignition is not instantaneous for high velocity plumes.
The wind influenced plume tests have measured 0.0005 kg/s hydrogen releases from 50 mm and 15 mm vent pipes. The largest hazardous zone for these releases stipulated in IGEM/SR/25 hydrogen supplement is Xr = 2.5 m and Xh = 1.5 m so these were used as the extent of measurement. With no wind the plume rises vertically from the vent tip with no radial deflection. Measured concentration peaks have exceeded the lower flammable limit (LFL) at the 1.5 m measurement height. The influence of wind radially displaces the plume the higher the wind the larger the displacement. Concentration peaks are reduced but a wind of 0.5 m/s still permitted levels above the 4 % LFL value. Wind levels of 1.0 m/s displaced the plume to the end of the 2.5 m measurement array. Wind levels of 1.5 m/s broke up the plumes potentially driving pockets of gas beyond the 2.5 m measurement array.
Partial ignition of both vent types was possible at 1.5 m above the vent tip but complete sustained ignition was only possible when closer than 1 m to the vent tip.
Plumes from higher pressure (above 0.1 barg) fixture and fitting leaks have shown a good correlation between the shapes of modelled and measured vents. Except for the lowest pressure leaks which are momentum-dominated jets the resulting plumes are long and thin unaffected by buoyancy. The concentration decay in measured plumes is observed to be faster with distance compared to modelled values. Typically the measured distance to reach 2 % volume from the leak position is about half of the specified zone distances.
Limited ignition tests have been conducted but ignition from a 2 barg adverse downward pointing leak was challenging beyond 30 cm from the leak. The hydrogen jet also repeatably extinguished the methane flame used as pilot light during tests.
The next steps for the project are to carry out more measurements and to scale up the magnitude of the gas releases. This will provide more evidence supporting specified magnitudes of hazardous zones. In addition it is proposed that mitigation measures are explored that could reduce the specified hazardous zones for given vents. This could include design guidelines for hydrogen vents.
Further ignition tests will also be conducted to assess required conditions such as flow direction and gas concentration required to achieve both partial and stable ignition of hydrogen vents.
This report was submitted to HSE for their assessment of the safety evidence for 100% hydrogen heating which can be found at Hydrogen heating: HSE assessment of the safety evidence - GOV.UK.
Queries should be directed to DESNZ: https://www.gov.uk/guidance/contact-desnz.
H21 Phase 2: Purging of Hydrogen Distribution Pipelines
Mar 2026
Publication
Over the last two years a significant programme of work has been undertaken as part of the H21 Phase 2 project to investigate purging of hydrogen distribution pipelines. The aim has been to undertake the underpinning science to support the development of safe and efficient purging procedures for hydrogen distribution pipelines. This report documents that scientific evidence-gathering process.
The report starts with a review of the existing pipeline purging practice and standards. Previous scientific work supporting the purging of town gas and natural gas distribution pipelines is reviewed. The properties of hydrogen are examined and previous work on hydrogen ignition potential and Deflagration to Detonation Transition (DDT) in pipes is assessed. The findings of the literature review are discussed and the decision to proceed with indirect (as opposed to direct) purging is explained.
This report was submitted to HSE for their assessment of the safety evidence for 100% hydrogen heating which can be found at Hydrogen heating: HSE assessment of the safety evidence - GOV.UK.
Queries should be directed to DESNZ: https://www.gov.uk/guidance/contact-desnz.
The report starts with a review of the existing pipeline purging practice and standards. Previous scientific work supporting the purging of town gas and natural gas distribution pipelines is reviewed. The properties of hydrogen are examined and previous work on hydrogen ignition potential and Deflagration to Detonation Transition (DDT) in pipes is assessed. The findings of the literature review are discussed and the decision to proceed with indirect (as opposed to direct) purging is explained.
This report was submitted to HSE for their assessment of the safety evidence for 100% hydrogen heating which can be found at Hydrogen heating: HSE assessment of the safety evidence - GOV.UK.
Queries should be directed to DESNZ: https://www.gov.uk/guidance/contact-desnz.
MOBs 357 Purging Hydrogen Risers (MOBS), Final Report
Mar 2026
Publication
Steer Energy and
SGN
Multiple Occupancy Buildings (MOBs) account for 21% of the UK’s domestic heating demand and tackling the challenge to decarbonise these properties will be key to meeting Government net zero targets.1 There is therefore a requirement for gas distribution network operators (GDNOs) to understand the cost safety and practicality of converting gas supplies to hydrogen. This project aimed to address evidence gaps centred around commissioning and decommissioning of risers associated with MOBs in particular purging operations.
The project has carried out a review of processes procedures and tooling used for purging MOBs examined site surveys and discussed purging with operators. Riser systems in MOBs are branched systems often comprising many vertical and horizontal elements taking a single supply source and distributing it to multiple individual dwellings in the building. Purging this network of elements is caried out in a routine manner as dictated by standards and procedures. Routine purging of MOBs is not challenging and this will continue to be the same when using hydrogen. The greatest challenge identified to purging MOBs is when each individual dwelling needs to be accessed to complete the purge. If an individual dwelling is inaccessible and individual lateral isolation valves are not installed then unpurged branches can remain. A consequence of leaving branches unpurged is a mixing of the air and fuel into a flammable mixture in the riser.
An experimental programme of work has been developed to investigate dispersion in unpurged branches of risers using methane and hydrogen. The experiments started with single pipes and developed in complexity to a branched system with six laterals. The main conclusions are: • If an unpurged branch is left over time the flammable volume at the interface between purged and unpurged sections will increase. Pipe diameter is the dominant parameter that dictates the speed of mixing of the two gases. • Gas dispersion occurs through a combination of buoyancy and diffusion buoyancy effects are diameter dependent becoming more dominant in pipe diameters greater than 50 mm. Below 50 mm gas dispersion is slow being dominated by diffusion alone. • Diffusion driven dispersion acts in the direction of concentration gradient from high to low. This acts to reduce the driving concentration gradient and slows down subsequent diffusion. In vertical pipes concentration gradients have been seen to act upwards or downwards. • Buoyancy effects act preferentially upwards but also promote mixing of different density gases in horizontal pipes. • In tests hydrogen dispersion was up to twice as fast as methane dispersion.
This report was submitted to HSE for their assessment of the safety evidence for 100% hydrogen heating which can be found at Hydrogen heating: HSE assessment of the safety evidence - GOV.UK.
Queries should be directed to DESNZ: https://www.gov.uk/guidance/contact-desnz.
The project has carried out a review of processes procedures and tooling used for purging MOBs examined site surveys and discussed purging with operators. Riser systems in MOBs are branched systems often comprising many vertical and horizontal elements taking a single supply source and distributing it to multiple individual dwellings in the building. Purging this network of elements is caried out in a routine manner as dictated by standards and procedures. Routine purging of MOBs is not challenging and this will continue to be the same when using hydrogen. The greatest challenge identified to purging MOBs is when each individual dwelling needs to be accessed to complete the purge. If an individual dwelling is inaccessible and individual lateral isolation valves are not installed then unpurged branches can remain. A consequence of leaving branches unpurged is a mixing of the air and fuel into a flammable mixture in the riser.
An experimental programme of work has been developed to investigate dispersion in unpurged branches of risers using methane and hydrogen. The experiments started with single pipes and developed in complexity to a branched system with six laterals. The main conclusions are: • If an unpurged branch is left over time the flammable volume at the interface between purged and unpurged sections will increase. Pipe diameter is the dominant parameter that dictates the speed of mixing of the two gases. • Gas dispersion occurs through a combination of buoyancy and diffusion buoyancy effects are diameter dependent becoming more dominant in pipe diameters greater than 50 mm. Below 50 mm gas dispersion is slow being dominated by diffusion alone. • Diffusion driven dispersion acts in the direction of concentration gradient from high to low. This acts to reduce the driving concentration gradient and slows down subsequent diffusion. In vertical pipes concentration gradients have been seen to act upwards or downwards. • Buoyancy effects act preferentially upwards but also promote mixing of different density gases in horizontal pipes. • In tests hydrogen dispersion was up to twice as fast as methane dispersion.
This report was submitted to HSE for their assessment of the safety evidence for 100% hydrogen heating which can be found at Hydrogen heating: HSE assessment of the safety evidence - GOV.UK.
Queries should be directed to DESNZ: https://www.gov.uk/guidance/contact-desnz.
NIA 346 H21 Hazardous Area Zoning Summary Report
Mar 2026
Publication
In order to utilise the existing gas transmission and distribution network to transport 100% hydrogen the effects of the changes in characteristics of hydrogen from natural gas need to be reviewed and the resultant effect on the network assessed. Hydrogen features a substantially larger range of flammable concentrations than natural gas which could potentially cause safety concerns if the existing network is not reviewed. Hazardous area zoning of equipment present on the gas transmission and distribution network is modelled in accordance with standard IGEM/SR/25 Ed. 2. A hazardous area is defined in this standard as “an area in which explosive gas/air mixtures are or may be expected to be in quantities as such as to require special precautions for the construction installation and use of electrical apparatus or other sources of ignition.” A supplement to this standard compatible with the use of hydrogen blends up to 20% in addition to pure hydrogen was published by IGEM in November 2022. This hydrogen supplement has been utilised to establish the hazardous area zoning of hydrogen gas in 13 sites across multiple networks.
Hydrogen possesses a lower molar mass than natural gas therefore the mass flow rate of gas escaping relief vent pipework during venting operations is expected to decrease during pressure-driven release. Due to the larger flammable concentration range of hydrogen-air mixtures the impact on the sizes of hazardous areas was not immediately present. Across all sites the size of hazardous areas was seen to increase upon calculating the hydrogen mass flow rate for a given vent. It was observed on several sites that the hazardous areas of relief vents extended beyond the site boundaries.
Additional consideration was paid to vent pipe geometry in relation to sections 7.8.3 and 7.8.4 of IGEM/TD/13 Ed. 2 Supplement 1 – Pressure Regulating Installations for Hydrogen at Pressures Exceeding 7 bar. These clauses require that the Length/Diameter ratio of a vent pipe be kept below 60:1 to reduce the chance of combustion or detonation due to depressurisation in the vent pipe. This is due to hydrogen experiencing an increase in temperature during depressurisation as opposed to natural gas which decreases in temperature. This affects all sites due to the prevalence of small-bore pipework (10-15mm) used in impulse and instrumentation pipework. This also has potential to affect smaller relief vent pipework such as that used on district governors (typically 1”/25NB) depending on specific pipe and valve placement.
This report was submitted to HSE for their assessment of the safety evidence for 100% hydrogen heating which can be found at Hydrogen heating: HSE assessment of the safety evidence - GOV.UK.
Queries should be directed to DESNZ: https://www.gov.uk/guidance/contact-desnz.
Hydrogen possesses a lower molar mass than natural gas therefore the mass flow rate of gas escaping relief vent pipework during venting operations is expected to decrease during pressure-driven release. Due to the larger flammable concentration range of hydrogen-air mixtures the impact on the sizes of hazardous areas was not immediately present. Across all sites the size of hazardous areas was seen to increase upon calculating the hydrogen mass flow rate for a given vent. It was observed on several sites that the hazardous areas of relief vents extended beyond the site boundaries.
Additional consideration was paid to vent pipe geometry in relation to sections 7.8.3 and 7.8.4 of IGEM/TD/13 Ed. 2 Supplement 1 – Pressure Regulating Installations for Hydrogen at Pressures Exceeding 7 bar. These clauses require that the Length/Diameter ratio of a vent pipe be kept below 60:1 to reduce the chance of combustion or detonation due to depressurisation in the vent pipe. This is due to hydrogen experiencing an increase in temperature during depressurisation as opposed to natural gas which decreases in temperature. This affects all sites due to the prevalence of small-bore pipework (10-15mm) used in impulse and instrumentation pipework. This also has potential to affect smaller relief vent pipework such as that used on district governors (typically 1”/25NB) depending on specific pipe and valve placement.
This report was submitted to HSE for their assessment of the safety evidence for 100% hydrogen heating which can be found at Hydrogen heating: HSE assessment of the safety evidence - GOV.UK.
Queries should be directed to DESNZ: https://www.gov.uk/guidance/contact-desnz.
H21 Phase2B T&M Pressure Regulation and Maintenance
Mar 2026
Publication
In line with the UK government’s de-carbonisation strategy Northern Gas Network’s (NGN) H21 project aims to demonstrate the feasibility of converting the existing <7barg gas distribution network to 100% hydrogen. Following progress on Phase 1 of the H21 programme Phase 2 was proposed to build on the knowledge acquired to provide further quantified safety-based evidence on the suitability of the GB networks to transport 100% hydrogen. Phase 2 consisted of a number of Project Phases. Phase 2b evaluates network operational procedures identifying which of these are suitable for a 100% hydrogen network and those that may require adjustments. To achieve this a gas demonstration network was built at South Bank Middlesbrough TS6 6LF to accommodate full scale network parameters and typical network components. A Master Test Plan (MTP) was subsequently developed by NGN in collaboration with the HSE and DNV to address various aspects of existing network procedures and operations including:
♦ Emergency Response and bad practice demonstrations
♦ Finding Leaks
♦ Accessing Leaks
♦ Assessment of repair techniques
♦ Planned live gas operations
♦ Isolation techniques
♦ Commissioning and decommissioning activities
♦ Pressure regulation and maintenance procedures
♦ Pressure and flow validation
Each of these areas of testing and assessments were then divided in individual tests or tasks and identified with a unique ID name.
This current report details the work conducted in the NGN H21 testing facility at South Bank in RedCar with the maintenance of a Honeywell MP-LP Twin Stream Governor. The programme included the maintenance functional checks and a major overhaul operation conducted on the twin stream governor. This was completed on the hydrogen network within the facility.
This report details the Honeywell Twin Stream Regulator and the flow demands in section 3. The demonstrations set-up maintenance procedure and method statement used in Section 4; the results and main observations in Section 5 followed by interpretation of results and conclusions in Section 6. Appendix A at the back of the document contains site evidence for the demonstration.
♦ Emergency Response and bad practice demonstrations
♦ Finding Leaks
♦ Accessing Leaks
♦ Assessment of repair techniques
♦ Planned live gas operations
♦ Isolation techniques
♦ Commissioning and decommissioning activities
♦ Pressure regulation and maintenance procedures
♦ Pressure and flow validation
Each of these areas of testing and assessments were then divided in individual tests or tasks and identified with a unique ID name.
This current report details the work conducted in the NGN H21 testing facility at South Bank in RedCar with the maintenance of a Honeywell MP-LP Twin Stream Governor. The programme included the maintenance functional checks and a major overhaul operation conducted on the twin stream governor. This was completed on the hydrogen network within the facility.
This report details the Honeywell Twin Stream Regulator and the flow demands in section 3. The demonstrations set-up maintenance procedure and method statement used in Section 4; the results and main observations in Section 5 followed by interpretation of results and conclusions in Section 6. Appendix A at the back of the document contains site evidence for the demonstration.
H21 ATEX-SR25 Summary Technical Report
Mar 2026
Publication
In order to utilise the existing gas transmission and distribution network to transport 100% hydrogen the effects of the changes in characteristics of hydrogen from natural gas need to be reviewed and the resultant effect on the network assessed. Hydrogen features a substantially larger range of flammable concentrations than natural gas which could cause safety concerns if the existing network is not reviewed.
By surveying the electrical and instrumentation assets on site it was identified that many of the existing instruments currently in operation are not certified for the hydrogen environment (minimum Gas Group IIC) and require replacement.
There are a large quantity of instruments not suitable for the hydrogen environment due to asset condition / age and the effect of corrosion overtime affecting instruments such as missing or illegible faceplates resulting in being unable to verify ATEX certifications. A smaller percentage of existing instrumentation are in good condition but not certified for the hydrogen environment.
Equipment without a faceplate have been considered as not suitable for Hydrogen pending a review of certification for validation within a hydrogen atmosphere a replacement may not be required.
This report was submitted to HSE for their assessment of the safety evidence for 100% hydrogen heating which can be found at Hydrogen heating: HSE assessment of the safety evidence - GOV.UK.
Queries should be directed to DESNZ: https://www.gov.uk/guidance/contact-desnz.
By surveying the electrical and instrumentation assets on site it was identified that many of the existing instruments currently in operation are not certified for the hydrogen environment (minimum Gas Group IIC) and require replacement.
There are a large quantity of instruments not suitable for the hydrogen environment due to asset condition / age and the effect of corrosion overtime affecting instruments such as missing or illegible faceplates resulting in being unable to verify ATEX certifications. A smaller percentage of existing instrumentation are in good condition but not certified for the hydrogen environment.
Equipment without a faceplate have been considered as not suitable for Hydrogen pending a review of certification for validation within a hydrogen atmosphere a replacement may not be required.
This report was submitted to HSE for their assessment of the safety evidence for 100% hydrogen heating which can be found at Hydrogen heating: HSE assessment of the safety evidence - GOV.UK.
Queries should be directed to DESNZ: https://www.gov.uk/guidance/contact-desnz.
H21 Phase 2A: Commissioning and Decommissioning Operations
Mar 2026
Publication
In line with the UK government's de-carbonisation strategy Northern Gas Network's (NGN) H21 project aims to enable the conversion of the UK gas networks to pure hydrogen. After conversion of the gas networks hydrogen is transported from various sources through new and existing gas networks to industrial and domestic customers.
Following progress on Phase 1 of the H21 programme Phase 2 consisted of a number of Project Phases. Phase 2a evaluates network operations tools and procedures identifying which of these are suitable for a 100% hydrogen network and those that may require adjustments. To achieve this a gas demonstration network was built at DNV Spadeadam Research and Testing to accommodate full scale network parameters and typical network components. A Master Test Plan (MTP) was subsequently developed by NGN in collaboration with the HSE S&RC and DNV to address various aspects of existing network procedures and operations including:
♦ Emergency Response and bad practice demonstrations
♦ Finding leaks
♦ Accessing leaks
♦ Assessment of repair techniques
♦ Live gas operations
♦ Isolation techniques
♦ Commissioning and decommissioning activities
♦ Pressure regulation and maintenance procedures
♦ Pressure and flow validation
Each of these areas of testing and assessments were then divided in individual tests or tasks and identified with a unique ID name.
The current report details the work conducted in the H21 demonstration grid at Spadeadam herein referred to as ""Microgrid"" in relation to commissioning and decommissioning activities. The programme included commissioning and decommissioning of straight mains branched networks and service pipes in each of the pressure tiers in the microgrid (IP MP and LP). In line with recommendations by the HSE S\&RC in their procedure review conducted earlier in Phase 2a; pipe diameters above 32 mm were commissioned or decommissioned indirectly (by displacing air with inert fluid followed by displacement of the inert fluid with hydrogen or vice versa). Pipe diameters under 32 mm (service pipe tests) were purged directly (air displaced by fuel gas or vice versa) according to a bespoke test procedure employing exclusion zones around pipes and vents.
Conversion style commissioning was also carried out in IP MP and LP mains i.e. converting pipes previously commissioned with Natural Gas to contain 100% hydrogen. This was also carried out by direct displacement of one fuel gas for the other.
This report was submitted to HSE for their assessment of the safety evidence for 100% hydrogen heating which can be found at Hydrogen heating: HSE assessment of the safety evidence - GOV.UK.
Queries should be directed to DESNZ: https://www.gov.uk/guidance/contact-desnz.
Following progress on Phase 1 of the H21 programme Phase 2 consisted of a number of Project Phases. Phase 2a evaluates network operations tools and procedures identifying which of these are suitable for a 100% hydrogen network and those that may require adjustments. To achieve this a gas demonstration network was built at DNV Spadeadam Research and Testing to accommodate full scale network parameters and typical network components. A Master Test Plan (MTP) was subsequently developed by NGN in collaboration with the HSE S&RC and DNV to address various aspects of existing network procedures and operations including:
♦ Emergency Response and bad practice demonstrations
♦ Finding leaks
♦ Accessing leaks
♦ Assessment of repair techniques
♦ Live gas operations
♦ Isolation techniques
♦ Commissioning and decommissioning activities
♦ Pressure regulation and maintenance procedures
♦ Pressure and flow validation
Each of these areas of testing and assessments were then divided in individual tests or tasks and identified with a unique ID name.
The current report details the work conducted in the H21 demonstration grid at Spadeadam herein referred to as ""Microgrid"" in relation to commissioning and decommissioning activities. The programme included commissioning and decommissioning of straight mains branched networks and service pipes in each of the pressure tiers in the microgrid (IP MP and LP). In line with recommendations by the HSE S\&RC in their procedure review conducted earlier in Phase 2a; pipe diameters above 32 mm were commissioned or decommissioned indirectly (by displacing air with inert fluid followed by displacement of the inert fluid with hydrogen or vice versa). Pipe diameters under 32 mm (service pipe tests) were purged directly (air displaced by fuel gas or vice versa) according to a bespoke test procedure employing exclusion zones around pipes and vents.
Conversion style commissioning was also carried out in IP MP and LP mains i.e. converting pipes previously commissioned with Natural Gas to contain 100% hydrogen. This was also carried out by direct displacement of one fuel gas for the other.
This report was submitted to HSE for their assessment of the safety evidence for 100% hydrogen heating which can be found at Hydrogen heating: HSE assessment of the safety evidence - GOV.UK.
Queries should be directed to DESNZ: https://www.gov.uk/guidance/contact-desnz.
No more items...